<br class="iwlinks"/>[[pl:Wyznaczanie temperatury przyległej przestrzeni|Wyznaczanie temperatury przyległej przestrzeni]][[de:Planung von Heizungsanlagen mit Konvektionsheizungen|Planung von Heizungsanlagen mit Konvektionsheizungen]][[fa:طراحی سیستم های گرمایشی با پایانه های همرفتی (رادیاتور و فن کویل)|طراحی سیستم های گرمایشی با پایانه های همرفتی (رادیاتور و فن کویل)]][[zh-cn:对流散热器供热系统的设计|对流散热器供热系统的设计]][[bg:Проектиране на отоплителни системи с конвекторни радиатори|Проектиране на отоплителни системи с конвекторни радиатори]]

Revision as of 16:00, 23 February 2026

Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2026-01-13


Problem description

The temperature of the adjacent space should be taken into account during Thermal calculations of building.
There are several variants to Determine temperature of adjacent space in the program:

  • Acc. to standard,
  • Acc. to standard Observe Δθij.,
  • Acc. to standard Limited to θj,u.,
  • Acc. to standard Observe Δθij. Limited to θj,u.,
  • Always adopt design temperature of adjacent space.

θj,u - minimum temperature of the adjacent space equals 16°C by default.


1. Determine temperature of adjacent space.


Note: Calculation variants above do not apply to rooms in a Building unit noted as Temperatures of adjacent spaces equal to design.

Solution

Acc. to standard

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,

θm,e - Annual mean external temperature.

2. Temperature on other side.



Acc. to standard Observe Δθij.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

If the calculated θos value is higher than the actual design Temperature on other side, the program for this section assumes the actual design temperatures (for both rooms).

Acc. to standard Limited to θj,u.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

If the calculated value of θos is lower than the declared value of θj,u, then the program assumes that θj,u is the temperature on the other side.

Acc. to standard Observe Δθij. Limited to θj,u.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

  • If the calculated value of θos is lower than the declared value of θj,u, then the program assumes that θj,u is the temperature on the other side,
  • If the calculated θos value, adjusted to reflect the point above, is higher than the actual design Temperature on other side, the program for this section assumes the actual design temperatures (for both rooms).

Always adopt design temperature of adjacent space

The program always assumes the actual calculated Temperature on other side.

The option "Temperatures of adjacent spaces equal to design" is chosen

If the option Temperatures of adjacent spaces equal to design is chosen , the program always accepts for the θos field the temperature value of the θi,H for the Room on the other side.

3. Temperatures of adjacent spaces equal to design.


The field "Room on other side"

There is the possibility to specify the type of the Room on other side:

  • %s (room of other building unit),
  • %s (room of other building) ,
  • %s (room of the same building unit).
    4. Room on other side.