Determination of adjacent space temperature: Difference between revisions

From HelpSystem
Jump to navigation Jump to search
No edit summary
No edit summary
Line 70: Line 70:
===<IS_TS id=26F7/>===
===<IS_TS id=26F7/>===
The program always assumes the actual calculated ''<IS_TS id=strl_expidISFPrzegrodaTemperaturaPoDrugiejStronie/>''.<br><br>
The program always assumes the actual calculated ''<IS_TS id=strl_expidISFPrzegrodaTemperaturaPoDrugiejStronie/>''.<br><br>
===The option "<IS_TS id=strs_boolidISFMieszkanieEN12831_TempZDrugiejStronyZawszeObliczane/>" is chosen===
The program always accepts for the ''<IS_TS id=strs_expidISFPrzegrodaTemperaturaPoDrugiejStronie_Uzytkownika/>'' field the temperature value of the ''<IS_TS id=strTempPomOgrzewanieSymbol/>'' for the ''<IS_TS id=iNameKonstrPomieszczenie/>'' on the other side.





Revision as of 08:08, 7 July 2025

Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2025-05-23


Problem description

The temperature of the adjacent space should be taken into account during Thermal calculations of building.
There are several variants to Determine temperature of adjacent space in the program:

  • Acc. to standard,
  • Acc. to standard Observe Δθij.,
  • Acc. to standard ,
  • Acc. to standard Observe Δθij. ,
  • Always adopt design temperature of adjacent space.

θj,u - minimum temperature of the adjacent space equals 16°C by default.


1. Determine temperature of adjacent space.


Note: Calculation variants above do not apply to rooms in a Building unit noted as Temperatures of adjacent spaces equal to design.

2. Temperatures of adjacent spaces equal to design.


Solution

Acc. to standard

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,

θm,e - Annual mean external temperature.

3. Temperature on other side.



Acc. to standard Observe Δθij.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

If the calculated θos value is higher than the actual design Temperature on other side, the program for this section assumes the actual design temperatures (for both rooms).

Acc. to standard

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

If the calculated value of θos is lower than the declared value of θj,u, then the program assumes that θj,u is the temperature on the other side.

Acc. to standard Observe Δθij.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

  • If the calculated value of θos is lower than the declared value of θj,u, then the program assumes that θj,u is the temperature on the other side,
  • If the calculated θos value, adjusted to reflect the point above, is higher than the actual design Temperature on other side, the program for this section assumes the actual design temperatures (for both rooms).

Always adopt design temperature of adjacent space

The program always assumes the actual calculated Temperature on other side.

The option "Temperatures of adjacent spaces equal to design" is chosen

The program always accepts for the θos field the temperature value of the θi,H for the Room on the other side.