==Problem description==
==Problem description==
The temperature of the adjacent space (''<IS_TS id=strl_expidISFPrzegrodaTemperaturaPoDrugiejStronie/>'' of the ''<IS_TS id=rsPrzegroda/>'') should be taken into account during [[Calculation_of_design_heat_load_of_rooms|<IS_TS id=ObliczeniaCieplneBudynku/>]].</br> There are several variants to ''<IS_TS id=rsEN12831_SposobWyznaczaniaTempZDrugiejStronyDlaInnychGrupPom/>'' in the program:
The temperature of the adjacent space should be taken into account during [[Calculation_of_design_heat_load_of_rooms|<IS_TS id=ObliczeniaCieplneBudynku/>]].</br> There are several variants to ''<IS_TS id=rsEN12831_SposobWyznaczaniaTempZDrugiejStronyDlaInnychGrupPom/>'' in the program:
* ''<IS_TS id=sNormowa/>'',
* ''<IS_TS id=sNormowa/>'',
* ''<IS_TS id=sNormowa/>'' ''<IS_TS id=26F5/>'',
* ''<IS_TS id=sNormowa/>'' ''<IS_TS id=26F5/>'',

Revision as of 06:32, 7 July 2025

Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2025-05-23


Problem description

The temperature of the adjacent space should be taken into account during Thermal calculations of building.
There are several variants to Determine temperature of adjacent space in the program:

  • Acc. to standard,
  • Acc. to standard Observe Δθij.,
  • Acc. to standard ,
  • Acc. to standard Observe Δθij. ,
  • Always adopt design temperature of adjacent space.
    1. Determine temperature of adjacent space.

Note: Calculation variants above do not apply to rooms in a Building unit noted as Temperatures of adjacent spaces equal to design.

2. Temperatures of adjacent spaces equal to design.


Solution

Acc. to standard

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,

θm,e - Annual mean external temperature.

3. Temperature on other side.


Acc. to standard Observe Δθij.

The Temperature on other side of the Partition located between rooms from different units is counted as follows:

θos = (θi,H + θm,e) / 2

θi,H - Design room temperature,
θm,e - Annual mean external temperature.

However, if the calculated θos value is higher than the actual design Temperature on other side, the program for this section assumes the actual design temperatures (for both rooms).

Acc. to standard

Acc. to standard Observe Δθij.

Always adopt design temperature of adjacent space