How to eliminate: "Cannot determine Dpmin on valve"

From HelpSystem
Jump to navigation Jump to search


Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2022-03-15


Problem description

Minimum pressure drop across the Valve component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. Δp controller) manufacturers recommend a specific value of Δpmin. For the calculation, the value is taken from the valve data table and can be changed individually there. Problems related to the program's inability to achieve the set Δpmin are identified by the message:

cannot determine Δpmin on valve


The above message appears when:

  • Valve has no settings (has a specified kv value) and has no thermostatic head,
  • for the smallest setting the flow through the Valve does not produce the required pressure drop.

Solution

W większości przypadków komunikat diagnostyki cannot determine Δpmin on valve można pozostawić bez "naprawy". W przypadku masowego występowania komunikatu dla elementu Valve na/przy odbiornikach, a więc gdy zachodzi obawa uzyskania zbyt niskich autorytetów, można:

  • użyć, o ile są dostępne, zaworów lub wkładek o mniejszym zakresie kv,
  • zwiększyć natężenie przepływu przez zakwestionowane odbiorniki, zmniejszając im obliczeniowy spadek temperatury. Jednak o ostatecznej wartości schłodzenia w odbiorniku decyduje opcja Adjust flow rates, która domyślnie jest włączona w oknie General data, Radiator sizing options.
    1. Adjust flow rates