How to eliminate: "Cannot determine Dpmin on valve": Difference between revisions
No edit summary |
No edit summary |
||
| Line 35: | Line 35: | ||
* use, if available, valves or integrated valves with a lower ''<IS_TS id=stringSpecOporyZnaneKv/>'' range,{{#ev:youtube|cHNbiKd7wvs|900||||rel=0}} | * use, if available, valves or integrated valves with a lower ''<IS_TS id=stringSpecOporyZnaneKv/>'' range,{{#ev:youtube|cHNbiKd7wvs|900||||rel=0}} | ||
* increase the flow rate through the terminal units in question by reducing their calculated temperature drop. However, the final cool down value in the terminal unit is determined by the ''<IS_TS id=sKorygujPrzeplywy/>'' option, which is enabled by default in the ''<IS_TS id=rsDanogi/>'', ''<IS_TS id=sOpcjeDoboruGrzejnikow/>'' window..<br/>[[File:Adjust-flow-rates.png|900 px|left|thumb|1. ''<IS_TS id=sKorygujPrzeplywy/>'']]<br clear="all"/> | * increase the flow rate through the terminal units in question by reducing their calculated temperature drop. However, the final cool down value in the terminal unit is determined by the ''<IS_TS id=sKorygujPrzeplywy/>'' option, which is enabled by default in the ''<IS_TS id=rsDanogi/>'', ''<IS_TS id=sOpcjeDoboruGrzejnikow/>'' window..<br/>[[File:Adjust-flow-rates.png|900 px|left|thumb|1. ''<IS_TS id=sKorygujPrzeplywy/>'']]<br clear="all"/> | ||
{|class="wikitable" style="width: 800px; margin: 0 auto;" | |||
!If you have any comments on this article, please send us a short message at ''info@instalsoft.com'' | |||
|} | |||
[[Category:InstalSystem 5]] | [[Category:InstalSystem 5]] | ||
Latest revision as of 15:26, 15 April 2026
| Product | InstalSystem 5 |
| Type of article | TIP&TRICK |
| Source for translation | 2022-03-15 |
Problem description
Minimum pressure drop across the Valve component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. Δp controller) manufacturers recommend a specific value of Δpmin. For the calculation, the value is taken from the valve data table and can be changed individually there. Problems related to the program's inability to achieve the set Δpmin are identified by the message:
cannot determine Δpmin on valve
The above message appears when:
- Valve has no settings (has a specified kv value) and has no thermostatic head,
- for the smallest setting the flow through the Valve does not produce the required pressure drop.
Solution
In most cases, the diagnostic message cannot determine Δpmin on valve can be left without responding to it. In the case of a mass occurrence of the message for the Valve component on/near the terminal units, and therefore when there is a concern of obtaining too low authorities, the following can be done:
- use, if available, valves or integrated valves with a lower kv range,
- increase the flow rate through the terminal units in question by reducing their calculated temperature drop. However, the final cool down value in the terminal unit is determined by the Adjust flow rates option, which is enabled by default in the General data, Radiator sizing options window..

1. Adjust flow rates