How to eliminate: "Max. working load %.1f exceeds permissible value %.1f for selected floor construction (insulation). Insulation was not determined": Difference between revisions

From HelpSystem
Jump to navigation Jump to search
No edit summary
No edit summary
Line 36: Line 36:


<!-- Do not write text below this tag -->
<!-- Do not write text below this tag -->
<br class="iwlinks"/>[[pl:Jak wyeliminować: "Maksymalne obciążenie użytkowe %.1f przekracza wartość dopuszczalną %.1f dla wybranej konstrukcji podłogi (izolacji). Nie udało się dobrać żadnego wariantu izolacji"|Jak wyeliminować: "Maksymalne obciążenie użytkowe %.1f przekracza wartość dopuszczalną %.1f dla wybranej konstrukcji podłogi (izolacji). Nie udało się dobrać żadnego wariantu izolacji"]][[bg:Как да елиминирате: "Макс. раб. товар %.1f надхвърля доп. стойност %.1f за избраната подова конструкция. Изолацията не беше определена"?|Как да елиминирате: "Макс. раб. товар %.1f надхвърля доп. стойност %.1f за избраната подова конструкция. Изолацията не беше определена"?]]
<br class="iwlinks"/>[[pl:Jak wyeliminować: "Maksymalne obciążenie użytkowe %.1f przekracza wartość dopuszczalną %.1f dla wybranej konstrukcji podłogi (izolacji). Nie udało się dobrać żadnego wariantu izolacji"|Jak wyeliminować: "Maksymalne obciążenie użytkowe %.1f przekracza wartość dopuszczalną %.1f dla wybranej konstrukcji podłogi (izolacji). Nie udało się dobrać żadnego wariantu izolacji"]][[zh-cn:如何删除: "地面最大工作载荷 %.1f 超过了选定的地面结构(绝热层)的允许值 %.1f,绝热材料未确定"|如何删除: "地面最大工作载荷 %.1f 超过了选定的地面结构(绝热层)的允许值 %.1f,绝热材料未确定"]]

Revision as of 08:02, 16 February 2026


Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2022-03-30


Problem description

Problems related to the design of the heating/cooling floor construction are indicated with the following message:

  • Max. working load %.1f exceeds permissible value %.1f for selected floor construction (insulation). Insulation was not determined.

Instead of the %.1f parameter, the load value in kN/m2 is displayed. The maximum value depends on the selected system, while the working load arises from the design data.

The diagnostic message is displayed when:

  • the default Max. working load specified in General data on the Floor systems tab exceeds the permissible load value listed in the catalogue for the given floor system;
  • Max. working load declared in Floor build-up ... for the selected Heating/Cooling Floor Zone exceeds the permissible load value listed in the catalogue for the given floor system.

Solution

  • Default maximum permissible operational load for underfloor systems is propagated to all Heating/Cooling Floor Zone components. When the message appears, the value for Max. working load can be changed in the General data window in the Floor systems section.
    1. Settings in the Max. working load field in the Floor systems tab.

  • Changes (decreases in value) can also be made only for selected Heating/Cooling Floor Zone components in the Max. working load field in the Floor build-up ... editor, launched from the Data table window.
    2. Setting values in the Max. working load field.