How to eliminate: "Cannot determine Dpmin on valve": Difference between revisions

From HelpSystem
Jump to navigation Jump to search
Line 20: Line 20:


==Problem description==
==Problem description==
''<IS_TS id=MinimalnySpadekCisnienia/>'' na elemencie ''<IS_TS id=pinNameZawor/>'' pomocny jest  - w przypadku zaworów przy lub na odbiornikach - w uzyskaniu wymaganego autorytetu, ponadto dla niektórych typów zaworów (np. ''<IS_TS id=rpRegulatorDP/>'') producenci zalecają określoną wartość ''<IS_TS id=sMinSpadekCisnienia/>''. Do obliczeń pobierana jest wartość z tabeli danych zaworu i tam można ją indywidualnie zmieniać.
''<IS_TS id=MinimalnySpadekCisnienia/>'' across the ''<IS_TS id=pinNameZawor/>'' component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. ''<IS_TS id=rpRegulatorDP/>'') manufacturers recommend a specific value of ''<IS_TS id=sMinSpadekCisnienia/>''. For the calculation, the value is taken from the valve data table and can be changed individually there.
 
Problems related to the program's inability to achieve the set ''<IS_TS id=sMinSpadekCisnienia/>'' are identified by the message:
Problemy związane z brakiem możliwości uzyskania przez program zadanego ''<IS_TS id=sMinSpadekCisnienia/>'' diagnozowane są za pośrednictwem komunikatu:


'''''<IS_TS id=strerrNieMogeUstanowicDPMinDlaZaworu/>'''''
'''''<IS_TS id=strerrNieMogeUstanowicDPMinDlaZaworu/>'''''


<br/>
<br/>
Powyższy komunikat pojawia się w przypadkach:
The above message appears when:
* gdy ''<IS_TS id=pinNameZawor/>'' jest bez nastaw (ma niezmienną wartość ''<IS_TS id=stringSpecOporyZnaneKv/>'') i nie ma głowicy termostatycznej,
* ''<IS_TS id=pinNameZawor/>'' has no settings (has a specified ''<IS_TS id=stringSpecOporyZnaneKv/>'' value) and has no thermostatic head,
* gdy dla najmniejszej nastawy przepływ przez ''<IS_TS id=pinNameZawor/>'' nie daje wymaganego spadku ciśnienia.
* for the smallest setting the flow through the ''<IS_TS id=pinNameZawor/>'' does not produce the required pressure drop.


==Solution==
==Solution==

Revision as of 19:03, 10 July 2022


Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2022-03-15


Problem description

Minimum pressure drop across the Valve component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. Δp controller) manufacturers recommend a specific value of Δpmin. For the calculation, the value is taken from the valve data table and can be changed individually there. Problems related to the program's inability to achieve the set Δpmin are identified by the message:

cannot determine Δpmin on valve


The above message appears when:

  • Valve has no settings (has a specified kv value) and has no thermostatic head,
  • for the smallest setting the flow through the Valve does not produce the required pressure drop.

Solution

W większości przypadków komunikat diagnostyki cannot determine Δpmin on valve można pozostawić bez "naprawy". W przypadku masowego występowania komunikatu dla elementu Valve na/przy odbiornikach, a więc gdy zachodzi obawa uzyskania zbyt niskich autorytetów, można:

  • użyć, o ile są dostępne, zaworów lub wkładek o mniejszym zakresie kv,
  • zwiększyć natężenie przepływu przez zakwestionowane odbiorniki, zmniejszając im obliczeniowy spadek temperatury. Jednak o ostatecznej wartości schłodzenia w odbiorniku decyduje opcja Adjust flow rates, która domyślnie jest włączona w oknie General data, Radiator sizing options.
    1. Adjust flow rates