How to eliminate: "Cannot determine Dpmin on valve": Difference between revisions
Muskietorzj (talk | contribs) |
No edit summary |
||
| (5 intermediate revisions by 3 users not shown) | |||
| Line 20: | Line 20: | ||
==Problem description== | ==Problem description== | ||
''<IS_TS id=MinimalnySpadekCisnienia/>'' | ''<IS_TS id=MinimalnySpadekCisnienia/>'' across the ''<IS_TS id=pinNameZawor/>'' component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. ''<IS_TS id=rpRegulatorDP/>'') manufacturers recommend a specific value of ''<IS_TS id=sMinSpadekCisnienia/>''. For the calculation, the value is taken from the valve data table and can be changed individually there. | ||
Problems related to the program's inability to achieve the set ''<IS_TS id=sMinSpadekCisnienia/>'' are identified by the message: | |||
'''''<IS_TS id=strerrNieMogeUstanowicDPMinDlaZaworu/>''''' | '''''<IS_TS id=strerrNieMogeUstanowicDPMinDlaZaworu/>''''' | ||
<br/> | <br/> | ||
The above message appears when: | |||
* | * ''<IS_TS id=pinNameZawor/>'' has no settings (has a specified ''<IS_TS id=stringSpecOporyZnaneKv/>'' value) and has no thermostatic head, | ||
* | * for the smallest setting the flow through the ''<IS_TS id=pinNameZawor/>'' does not produce the required pressure drop. | ||
==Solution== | ==Solution== | ||
In most cases, the diagnostic message ''<IS_TS id=strerrNieMogeUstanowicDPMinDlaZaworu/>'' can be left without responding to it. In the case of a mass occurrence of the message for the ''<IS_TS id=pinNameZawor/>'' component on/near the terminal units, and therefore when there is a concern of obtaining too low authorities, the following can be done: | |||
* use, if available, valves or integrated valves with a lower ''<IS_TS id=stringSpecOporyZnaneKv/>'' range,{{#ev:youtube|cHNbiKd7wvs|900||||rel=0}} | |||
* increase the flow rate through the terminal units in question by reducing their calculated temperature drop. However, the final cool down value in the terminal unit is determined by the ''<IS_TS id=sKorygujPrzeplywy/>'' option, which is enabled by default in the ''<IS_TS id=rsDanogi/>'', ''<IS_TS id=sOpcjeDoboruGrzejnikow/>'' window..<br/>[[File:Adjust-flow-rates.png|900 px|left|thumb|1. ''<IS_TS id=sKorygujPrzeplywy/>'']]<br clear="all"/> | |||
{|class="wikitable" style="width: 800px; margin: 0 auto;" | |||
!If you have any comments on this article, please send us a short message at ''info@instalsoft.com'' | |||
|} | |||
[[Category:InstalSystem 5]] | [[Category:InstalSystem 5]] | ||
| Line 41: | Line 46: | ||
<!-- Do not write text below this tag --> | <!-- Do not write text below this tag --> | ||
<br class="iwlinks"/>[[pl:Jak wyeliminować: "Nie można ustalić Dpmin na zaworze"|Jak wyeliminować: "Nie można ustalić Dpmin na zaworze"]] | <br class="iwlinks"/>[[pl:Jak wyeliminować: "Nie można ustalić Dpmin na zaworze"|Jak wyeliminować: "Nie można ustalić Dpmin na zaworze"]][[fa:Dp min|Dp min]][[zh-cn:如何删除:"不能确定阀门上的最小压降ΔP最小"|如何删除:"不能确定阀门上的最小压降ΔP最小"]][[bg:Как да елиминирате: "не може да определи Dpmin на вентил"?|Как да елиминирате: "не може да определи Dpmin на вентил"?]] | ||
Latest revision as of 15:26, 15 April 2026
| Product | InstalSystem 5 |
| Type of article | TIP&TRICK |
| Source for translation | 2022-03-15 |
Problem description
Minimum pressure drop across the Valve component is helpful, in the case of valves installed near or on terminal units, in obtaining the required authority; in addition, for some valve types (e.g. Δp controller) manufacturers recommend a specific value of Δpmin. For the calculation, the value is taken from the valve data table and can be changed individually there. Problems related to the program's inability to achieve the set Δpmin are identified by the message:
cannot determine Δpmin on valve
The above message appears when:
- Valve has no settings (has a specified kv value) and has no thermostatic head,
- for the smallest setting the flow through the Valve does not produce the required pressure drop.
Solution
In most cases, the diagnostic message cannot determine Δpmin on valve can be left without responding to it. In the case of a mass occurrence of the message for the Valve component on/near the terminal units, and therefore when there is a concern of obtaining too low authorities, the following can be done:
- use, if available, valves or integrated valves with a lower kv range,
- increase the flow rate through the terminal units in question by reducing their calculated temperature drop. However, the final cool down value in the terminal unit is determined by the Adjust flow rates option, which is enabled by default in the General data, Radiator sizing options window..

1. Adjust flow rates