Pipe-run

From HelpSystem
Jump to navigation Jump to search


Product InstalSystem 5
Type of article FUNCTIONS AND TOOLS
Source for translation 2023-01-10


Description

Pipe-run is a component that is available within all design scopes, it forms a fragment of the piping system between two junctions where the flow can be changed. Within the following scopes: Heating systems, Cooling systems and Water supply systems a Pipe-run may consist of multiple segments (vertical and horizontal), separated by pipe-run division points. It can be drawn as a single pipe-run or as a Pipe-runs pair/ Three pipe-runs. Within the Sanitary drainage systems scope a Pipe-run of the Gravity sewerage or Ventilation conduit type always consists of a single segment.
It is possible to specify default values for Distance from floor (set in storey data). In addition, the user has full control over the arrangement of the pipe-runs using dedicated editors available in the 2D editor and 3D view windows.

Location in the program

Inserting pipe-runs

  • Icons associated with Pipe-run, with Project scope: Heating systems or Cooling systems activated, are available in the 2D editor window in the Main tools bar, section Distribution - thermal installations when the following editing scopes are enabled: Convectional, Rad.-floors,walls or Rad.-ceilings.
    1. Pipe-run - Heating systems or Cooling systems.

  • Icons associated with Pipe-run, with Water supply systems activated, are available in the 2D editor window in the Main tools bar, section Distribution - Water supply when the Water supply editing scope is enabled.
    2. Pipe-run - Water supply systems.

  • Icons associated with Pipe-run, with Sanitary drainage systems activated, are available in the 2D editor window in the Main tools bar, section Sanitary drainage when the Drainage (S) editing scope is enabled.
    3. Pipe-run - Sanitary drainage systems.

Examples of use

Pipe-run dividing point and midpoint

  • One Pipe-run may consist of several sections connected by means of midpoints.
  • Two Pipe-run are separated by a pipe-run dividing point - a junction/node.
  • Any number of additional points can be placed on a Pipe-run using the context menu and functions available there: Insert midpoint and Insert dividing point.
  • Midpoints can be changed into dividing points and vice versa:

Default distances between pipe-run and floor and between pipe-run and ceiling

In the Data table window it is possible to specify for a Storey the default distance from the floor separately for each Pipe-run type component and the default distance from the ceiling (for arranging ceiling panels) in the following fields:

  • for Heating systems:
    • ΔHpipe-run,,S and ΔHpipe-run,, R - Default distance of pipe-runs (except for supplying ceiling panels) from the floor specified in storey data: S - supply, R - return.
    • ΔHpipe-run,pan. - Pipe-run to ceiling distance - ceiling panel distribution.
  • for Water supply systems:
    • ΔHpipe-run,,HW - Default pipe-run distance from the floor (set in storey data) for Pipe-run: Hot water.
    • ΔHpipe-run,,CW - Default pipe-run distance from the floor (set in storey data) for Pipe-run: Cold water.
    • ΔHpipe-run,,Circ - Default pipe-run distance from the floor (set in storey data) for Pipe-run: Circulation.
      4. Default pipe-run distance.

Pipe-run laying distance

  • The Distance between pipe-runs can be specified for Pipe-runs pair/Three pipe-runs in the Data table window. After each component inserted, the last specified Distance is memorized.
    5. Distance for Pipe-runs pair.

Determining the vertical alignment of the pipe-runs - Heating systems, Cooling systems and Water supply systems

The alignment and elevations of a pipe-run can be managed using dedicated editors that are displayed after selecting a component in the 2D editor and 3D view window:

  • - shows the elevation of the pipe-run end.
  • - shows the elevation of the section.
  • - shows the distance between pipe-run point/section and floor.
    6. Display of the elevations of a Pipe-run in the 2D editor and 3D view window.

InstalSystem 5 offers three methods of managing the alignment of a distribution system that allow the most convenient method to be selected to suit the individual design context. The method should be selected in the Vertical layout of pipe-run editor in the Data table window for the Pipe-run:

  • Auto mode:
    • Editors showing the elevation of pipe-run ends and distance from the floor are greyed out and the values presented cannot be modified.
    • The value of Elevation can be modified in the Data table window for the Pipe-run and this change automatically modifies the values in all editors for the selected component.

  • Manual elevations of sections mode:
    • In the editors available in the 2D editor and 3D view window it is possible to specify the elevation and distance from the floor of a pipe-run section.
    • Based on the difference between the specified section elevations, vertical pipe-runs are automatically created.
    • Editors of pipe-runs connected on one end to terminal units are greyed out and these cannot be edited.
    • The 2D editor and 3D view windows do not display editors with elevations of vertical sections of pipe-runs.
      7. Vertical layout of pipe-run - Manual elevations of sections.

  • Manual elevations of nodes:
    • Editors in the 2D editor and 3D view window enable specifying the elevations and distance from the floor of the ends of a Pipe-run section.
    • Vertical sections of pipe-runs are NOT automatically created - the entire pipe-run layout is controlled by the user.
    • Editors of pipe-runs connected on one end to terminal units are greyed out and these cannot be edited.
      8. Vertical layout of pipe-run - Manual elevations of nodes.

Attention! Every change of elevations and modification of Pipe-run layout requires running a Check connections operation available on the Main tools bar in section Calculations.


Determining the vertical alignment of pipe-runs - Sanitary drainage systems

The elevations and gradient of a pipe-run can be managed using dedicated editors that are displayed after selecting a component in the 2D editor and 3D view window:

  • - shows the elevation of pipe-run sections, values presented in the editors correspond to the fields: Elevation of first node and Elevation of second node available in the Data table window of the component.
  • - shows the gradient of the pipe-run and corresponds to the Real gradient field available in the Data table window of the component.
    5. Display of elevations and gradient of a Pipe-run in the 2D editor and 3D view window.

When laying the pipe-runs, they adopt a gradient according to the direction of flow to the sewage outlet, taking into account the settings made in the General data window on the Sanitary drainage systems/ Calculation standards and options tab:

  • The default minimum gradients specified for the selected component locations are adopted. In addition, the pipe-run laying algorithm takes into account the elevation and gradient values specified by the user in the editors described above.
  • The Method of conducting of branches is taken into account:
    • for the towards the floor setting - pipe-runs are arranged towards the terminal units with minimum gradient. If necessary, vertical pipe-runs at the terminal units are added taking into account the value specified in Distance from the floor of the connection points to the stack field,
    • for the towards the wall setting - pipe-runs are arranged downstream of the terminal unit with the gradients specified in the General data window, and they are then connected to the collective branch by means of a vertical pipe-run (if drawing it is necessary for the continuity of the system).
      9. Alignment of pipe-runs - Sanitary drainage systems.

Laying pipe-runs in a single vertical plane

  • Appropriate setting of elevation values of individual types of pipe-runs in the Data table window for a Storey in sections: Heating/Cooling or Water supply and specifying the minimum value in the Distance field in the Data table window of a Pipe-runs pair/ Three pipe-runs, enable aligning pipe-runs in one vertical plane, e.g. in a wall one over the other.

Inclined pipe-runs

  • The Vertical layout of pipe-run function enables full control over the alignment of a pipe-run, which, together with the possibility of marking points on a component, makes it possible to draw inclined pipe-runs and to design the connections of systems located on inclined attic elements.

Basic rules of connecting pipe-runs to other system components

The Main tools bar in the Edit group offers three methods of automatic connecting of terminal units to the pipe-run arrangement drawn beforehand:

10. Connecting panels in an attic.


  • Automatically connect terminal units - connects selected Pipe-run components and terminal units within the following scopes: Heating systems, Cooling systems and Water supply systems.
  • Automatically connect terminal units in tee system - connects selected Pipe-run components and terminal units of a water supply system in a tee joint system.
  • Connect in series - connects Ceiling panel or Wall panel components selected beforehand using a Serial connection type pipe-run. For more information, see: Designing panel (ceiling, wall) heating/cooling systems.

For all components connected to a system (e.g. Terminal unit, Mixer, Manifold), a horizontal pipe-run section 5cm long is drawn, followed by a bend to arrive at the defined elevation of the Pipe-run. Exceptions from this rule:

  • Connection of a Radiator with an integrated angled valve - a horizontal pipe-run section is drawn of a length of: Distance from wall + 5cm, followed by a bend to arrive at the defined elevation of the Pipe-run.
  • Connection of a Water supply faucet - a horizontal pipe-run section 1cm long is drawn, followed by a bend to arrive at the defined elevation of the Pipe-run.
    11. Connection of a Water supply faucet.

  • Connection of a Riser - if the pipe-run connection is made directly, with no midpoints, the pipe-run elevation adopted corresponds to the actual value in accordance with the data given in the Data table window of the Pipe-run.
  • Connection of a Mixer/Control loop - the Automatically connect terminal units operation results in connecting only the points that are on the primary side of the Mixer.

Pipe-run in auto mode

When pipe-runs have been drawn in a project in such a way that within one storey there are vertical pipe-runs (created not by inserting a Riser, but by connecting four pipe-runs or pipe-run pairs), pipe-runs to be connected to these vertical sections are subject to defined drawing rules:

  • when drawing components with the Auto mode enabled, the Pipe-run is connected to the vertical pipe-run with its elevation retained.
  • when connecting a pipe-run to pipe-runs the coordinates of which overlap, the Pipe-run drawn is connected to the component of the lowest elevation.
    12. Connection to vertical pipe-runs.

No-flow and bypass pipe runs

No medium flow pipe-run

  • Is used in Water supply systems, Heating systems and Cooling systems for drainage and removal of condensate and is available in the appropriate project scopes.
    13. No medium flow pipe-run.

  • One end of this type of pipe should be connected to a standard pipe-run, the other end to one of the following elements:
    • Expansion vessel;
    • Safety valve;
    • Outlet of no-flow pipe-run.
  • Can be fitted with Shut-off valves.

By-pass pipe-run

  • Is used in Heating systems and Cooling systems for redirecting the medium flow and is available in the appropriate project scopes. Is not used for mixing (is a kind of No medium flow pipe-run).
    14. By-pass pipe-run.

  • Can be connected to Pipe-run (supply) and Pipe-run (return) or two pipes of the same type (valve bypass).
  • Can be fitted with the several types of valves, including Shut-off valves and Relief valve.