Heat source dimensioning
Revision as of 07:34, 15 December 2022 by Klintsevicho (talk | contribs)
| Product | InstalSystem 5 |
| Type of article | TIP&TRICK |
| Source for translation | 2022-12-14 |
Problem description
The way in which the heat source is dimensioned depends on the type of designed installation and on the Method of calculating Φ specified in the General data window.

Solution
Heating installations without Flat stations
For dimensioning the heat source the following values should be taken into account:
- Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard;

2. Design heat load of building for the installations without Flat stations. - The total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified.

3. Spec. total rooms heat loss ΦH for the installations without Flat stations.

Heating installations with Flat stations
For such type of installations there are two variants for the heat source dimensioning in the heating period:
- If the heat source lacks a buffer tank - heat source dimensioning should adopt the Total output value;

5. Total output for the installations with Flat stations. - If the heat source includes a buffer tank - the indicated Total output value is the peak power that the buffer tank is supposed to deliver to the installation. For dimensioning the heat source the following values should be taken into account:
- Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard

6. Design heat load of building for the installations with Flat stations. - The total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified

7. Spec. total rooms heat loss ΦH for the installations with Flat stations.

Total output of heat exchangers in flat stations in summer
In the summer period when there is no need of heating, it is possible to reduce the heating output ordered from the heat supplier. The value of Total output of heat exchangers in flat stations in summer can be found in the General results heating.