Heat source dimensioning: Difference between revisions

From HelpSystem
Jump to navigation Jump to search
Line 28: Line 28:


===Heating installations with <IS_TS id=StacjeMieszkaniowe/>===
===Heating installations with <IS_TS id=StacjeMieszkaniowe/>===
For such type of installations there are two variants for a heat source dimensioning in the heating period:
For such type of installations there are two variants for a heat source dimensioning in the ''heating period'':
* If the heat source lacks a buffer tank - heat source dimensioning should adopt the  ''<IS_TS id=sMocCalkowitaZr/>'' value; <br/>[[File:HS dimensioning Total output.png|900 px|left|thumb|5. <IS_TS id=sMocCalkowitaZr/> for the installations with <IS_TS id=StacjeMieszkaniowe/>.]]<br clear="all"/>
* If the heat source lacks a buffer tank - heat source dimensioning should adopt the  ''<IS_TS id=sMocCalkowitaZr/>'' value; <br/>[[File:HS dimensioning Total output.png|900 px|left|thumb|5. <IS_TS id=sMocCalkowitaZr/> for the installations with <IS_TS id=StacjeMieszkaniowe/>.]]<br clear="all"/>
* If the heat source includes a buffer tank - the indicated ''<IS_TS id=sMocCalkowitaZr/>'' value is the peak power that the buffer tank is supposed to deliver to the installation. For dimensioning the heat source the following values should be taken into account:
* If the heat source includes a buffer tank - the indicated ''<IS_TS id=sMocCalkowitaZr/>'' value is the peak power that the buffer tank is supposed to deliver to the installation. For dimensioning the heat source the following values should be taken into account:

Revision as of 13:49, 14 December 2022

Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2022-12-14


Problem description

The way in which the heat source is dimensioned depends on the type of designed installation and on the Method of calculating Φ specified in the General data window.

1. Method of calculating Φ selection.


Solution

Heating installations without Flat stations

For dimensioning the heat source the following values should be taken into account:

  • Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard;
    2. Design heat load of building for the installations without Flat stations.

  • the total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified.
    3. Spec. total rooms heat loss ΦH for the installations without Flat stations.

4. Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area for the installations without Flat stations.


Heating installations with Flat stations

For such type of installations there are two variants for a heat source dimensioning in the heating period:

  • If the heat source lacks a buffer tank - heat source dimensioning should adopt the Total output value;
    5. Total output for the installations with Flat stations.

  • If the heat source includes a buffer tank - the indicated Total output value is the peak power that the buffer tank is supposed to deliver to the installation. For dimensioning the heat source the following values should be taken into account:
  • Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard
    6. Design heat load of building for the installations with Flat stations.

  • the total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified
    7. Spec. total rooms heat loss ΦH for the installations with Flat stations.

8. Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area for the installations with Flat stations.