==Examples of use==
==Examples of use==
Dostępne zakresy obliczeń interaktywnych i możliwość edycji okien na poszczególnych zakresach edycji są uzależnione od wybranego zastosowania w źródle. <br clear="all"/>
Which interactive calculations are possible and which windows are editable depends on the selected use of source. <br clear="all"/>
# Zastosowanie ''<IS_TS id=strNazwaWarstwyInstalacjiCOOP/>'' - w oknie ''<IS_TS id=ShowInteractiveCalculationWindow/>'' jest możliwość zmiany parametrów na zakładce Ogrzewanie, zakładka Chłodzenie jest pusta. {{#ev:youtube|BvjTpc96Vds|900||||rel=0}} <br clear="all"/>  
# ''<IS_TS id=strNazwaWarstwyInstalacjiCOOP/>'' use - in the ''<IS_TS id=ShowInteractiveCalculationWindow/>'' window it is possible to modify parameters in the Heating tab, the Cooling tab is empty. {{#ev:youtube|BvjTpc96Vds|900||||rel=0}} <br clear="all"/>  
# Zastosowanie ''<IS_TS id=OgrzewanieZChlodzeniem/>'' -  w oknie ''<IS_TS id=ShowInteractiveCalculationWindow/>'' jest możliwość zmiany parametrów na zakładce Ogrzewanie, na zakładce Chłodzenie są widoczne wszystkie wartości, ale nie ma możliwości ich edycji. {{#ev:youtube|7GcwMezcaCw|900||||rel=0}} <br clear="all"/>  
# ''<IS_TS id=OgrzewanieZChlodzeniem/>'' use in the ''<IS_TS id=ShowInteractiveCalculationWindow/>'' window it is possible to modify parameters in the Heating tab, the Cooling tab displays all values, but these cannot be modified. {{#ev:youtube|7GcwMezcaCw|900||||rel=0}} <br clear="all"/>  
# Zastosowanie ''<IS_TS id=Chlodzenie/>'' - w oknie ''<IS_TS id=ShowInteractiveCalculationWindow/>'' jest możliwość zmiany parametrów na zakładce Chłodzenie, zakładka Ogrzewanie jest pusta.  {{#ev:youtube|WkR6WotxWHY|900||||rel=0}} <br clear="all"/>   
# ''<IS_TS id=Chlodzenie/>'' use - in the ''<IS_TS id=ShowInteractiveCalculationWindow/>'' window it is possible to modify parameters in the Cooling tab, the Heating tab is empty.  {{#ev:youtube|WkR6WotxWHY|900||||rel=0}} <br clear="all"/>   
Inne możliwości dostępne w oknie ''<IS_TS id=ShowInteractiveCalculationWindow/>''<br clear="all"/>
Other possibilities in the ''<IS_TS id=ShowInteractiveCalculationWindow/>'' window<br clear="all"/>
#Filtrowanie SPGch podpiętych do danego rozdzielacza.<br/>[[File:Double apartment manifold list.png|900 px|left|thumb|5. Filtrowanie ''<IS_TS id=iNameOPStrefaPowGrzejnych/>''podpiętych do danego rozdzielacza.]]<br clear="all"/>
#Filtering H/C areas connected to given manifold.<br/>[[File:Double apartment manifold list.png|900 px|left|thumb|5. Filtering ''<IS_TS id=iNameOPStrefaPowGrzejnych/>'' connected to given manifold.]]<br clear="all"/>
#Powrót do ustawień automatycznych obliczeń -  ''<IS_TS id=ResetToAuto/>''.<br/>[[File:Restore_AUTO_settings.png|900 px|left|thumb|6. ''<IS_TS id=ResetToAuto/>'']]<br clear="all"/>
#Restoration of automatic calculation settings -  ''<IS_TS id=ResetToAuto/>''.<br/>[[File:Restore_AUTO_settings.png|900 px|left|thumb|6. ''<IS_TS id=ResetToAuto/>'']]<br clear="all"/>


===Korekta liczby Powierzchni Grzewczo-Chłodzących===
===Adjustment of the number of Heating/Cooling Areas===
* W przypadku ręcznej zmiany ilości PGCh, przywracane są ustawienia domyślne wartości  ''<IS_TS id=strDeltaThetaLong/>'' (status komputer) dla wszystkich PGCh należącej do danej SPGCh.<br/>{{#ev:youtube|ZeuXaRiSPkU|900||||rel=0}} <br clear="all"/>
* When the number of H/C Areas is changed manually, the default values of ''<IS_TS id=strDeltaThetaLong/>'' (computer status) are restored for all H/C Areas belonging to given H/C Areas Zone.<br/>{{#ev:youtube|ZeuXaRiSPkU|900||||rel=0}} <br clear="all"/>


===Korekta odstępów układania===
===Adjustment of pipe spacing===
* W wyniku ręcznej korekty parametru ''<IS_TS id=strVALong/>'' program może zmienić wartość dla parametru ''<IS_TS id=strPGCh/>'', ale nie wyłącza trybu podziału automatycznego elementu ''<IS_TS id=strSPGCh/>''.<br/> Zmiana wartości ''<IS_TS id=strVALong/>'' w ramach pojedynczego elementu ''<IS_TS id=strPGCh/>'' zmienia ten parametr we wszystkich występujących ''<IS_TS id=strPGChShort/>'' w ramach wspólnego elementu ''<IS_TS id=strSPGCh/>''.<br/>{{#ev:youtube|7UNU_WXFbG4|900||||rel=0}} <br clear="all"/>
* As a result of manual adjustment of ''<IS_TS id=strVALong/>'' the program can change the value of ''<IS_TS id=strPGCh/>'', but the automatic mode of ''<IS_TS id=strSPGCh/>'' division is not disabled.<br/> Change in the value of ''<IS_TS id=strVALong/>'' in a single ''<IS_TS id=strPGCh/>'' changes that parameter in all  ''<IS_TS id=strPGChShort/>'' elements present within the common ''<IS_TS id=strSPGCh/>''.<br/>{{#ev:youtube|7UNU_WXFbG4|900||||rel=0}} <br clear="all"/>


===Korekta wartości ''<IS_TS id=strDeltaThetaLong/>'' ===
===Adjustment of ''<IS_TS id=strDeltaThetaLong/>'' ===
* Zmiana tej wartości może między innymi wpłynąć na eliminację komunikatu diagnostyki:<br/>
* Modification of this value may, among other things, have an effect on the elimination of the diagnostics message:<br/>
** ''<IS_TS id=strWrnPowGrzejnaMHLow/>''.<br/>{{#ev:youtube|V72yHpbl6bU|900||||rel=0}} <br clear="all"/>
** ''<IS_TS id=strWrnPowGrzejnaMHLow/>''.<br/>{{#ev:youtube|V72yHpbl6bU|900||||rel=0}} <br clear="all"/>



Revision as of 10:50, 20 October 2020

Product InstalSystem 5
Type of article FUNKCJA I NARZĘDZIE
Source for translation GOLD Rev. 17.1


Description

Interactive radiant systems calculations enables fast manual adjustment of selected parameters of a radiant system in given application (Heating/Cooling). In the Interactive radiant systems calculations window the following can be adjusted:

  • pipe spacing calculated by the program,
  • the value of Temp. diff. supply-return
  • the value of No. of H/C Areas.
    1. Interactive calculations window-heating tab

    2. Interactive calculations window-cooling tab

After modifying any of these parameters and clicking Calculate, only the minimum required set of calculations is made:

  • pressure drops in the radiant heating/cooling loops are balanced only in relation to each other across the manifold.
    Pressure drops across the manifold balancing valves are calculated under the assumption that the pressure at the manifold inlet is equal to the required minimum available pressure for this manifold.
    After these calculations pressure drops are recalculated with flow calculations made for the entire system, when the pressure at the manifold often turns out to be higher than the required minimum available pressure.

For this reason, after closing Interactive radiant systems calculations:

  • calculations must be run, as the project has an uncalculated status, which is indicated, for instance, in the status bar:
    Attention! The project has not been calculated or data have been modifed since last calculation..


Location in the program

  • The Interactive radiant systems calculations icon is available in the Main tools bar in section Calculations.
    3. Interactive radiant systems calculations

  • Keyboard shortcut: Ctrl + Shift + F10.

Examples of use

Which interactive calculations are possible and which windows are editable depends on the selected use of source.

  1. Heating use - in the Interactive radiant systems calculations window it is possible to modify parameters in the Heating tab, the Cooling tab is empty.

  2. Heating and cooling efficiency use - in the Interactive radiant systems calculations window it is possible to modify parameters in the Heating tab, the Cooling tab displays all values, but these cannot be modified.

  3. Cooling use - in the Interactive radiant systems calculations window it is possible to modify parameters in the Cooling tab, the Heating tab is empty.

Other possibilities in the Interactive radiant systems calculations window

  1. Filtering H/C areas connected to given manifold.
    5. Filtering Heating/Cooling Zone connected to given manifold.

  2. Restoration of automatic calculation settings - Restore AUTO settings.
    6. Restore AUTO settings

Adjustment of the number of Heating/Cooling Areas

  • When the number of H/C Areas is changed manually, the default values of Temp. diff. supply-return (computer status) are restored for all H/C Areas belonging to given H/C Areas Zone.

Adjustment of pipe spacing

  • As a result of manual adjustment of Pipe spacing the program can change the value of Heating-cooling surface, but the automatic mode of Heating/Cooling Zone division is not disabled.
    Change in the value of Pipe spacing in a single Heating-cooling surface changes that parameter in all H/C Area elements present within the common Heating/Cooling Zone.

Adjustment of Temp. diff. supply-return

  • Modification of this value may, among other things, have an effect on the elimination of the diagnostics message:
    • water velocity in pipe not sufficient for self-venting.

Dodatkowe informacje

Konsekwencją korekty parametrów w Interactive radiant systems calculations jest rezygnacja z optymalnego wariantu wyznaczania temperatury zasilania dla instalacji płaszczyznowej wg wybranego kryterium w General data:

  • heat output and press. drop,
  • min. investment costs.

Ta rezygnacja z optymalnego wariantu jest diagnozowana przez program komunikatami diagnostyki o randze podpowiedzi:

  • there is a better spacing in heat output terms than the one specified,
  • there is a better spacing in cost terms than the one specified,
  • there is a better spacing in heat output and flow terms than the one specified.

Zawartość listy komunikatów diagnostyki w oknie Interactive radiant systems calculations oraz w oknie Diagnostics programu może się różnić. Ewentualne korekty w projekcie powinny opierać się o listę komunikatów po wykonaniu obliczeń dla odpowiedniego zakresu projektu np. "Instalacje grzewcze i chłodnicze", czyli w oknie Diagnostics.

Zasady wyróżnienia pól, które można edytować w oknie obliczeń:

  • Zmiana wartości w polu powoduje podświetlenie komórki na inny kolor i prezentacje tej wartości.
    6. Prezentacja pola z wartością wprowadzoną ręcznie tuż po edycji

  • Po przeliczeniu wartości bez wyróżnienia kolorystycznego.
    7. Prezentacja pola z wartością wprowadzoną ręcznie po obliczeniach