Heat source dimensioning: Difference between revisions

From HelpSystem
Jump to navigation Jump to search
No edit summary
No edit summary
Line 37: Line 37:
In summer period, when the flat stations are operating in DHW heating mode, the heating capacity ordered from the heat source can be reduced. The value of ''<IS_TS id=SumaMocyCWUStacjiWTrybieCWU/>'' can be found in the ''<IS_TS id=strWynikiOgolneOgrzewania/>''.<br/>[[File:HS dimensioning Total output summer fs.png|900 px|left|thumb|9. <IS_TS id=SumaMocyCWUStacjiWTrybieCWU/>.]]<br clear="all"/>
In summer period, when the flat stations are operating in DHW heating mode, the heating capacity ordered from the heat source can be reduced. The value of ''<IS_TS id=SumaMocyCWUStacjiWTrybieCWU/>'' can be found in the ''<IS_TS id=strWynikiOgolneOgrzewania/>''.<br/>[[File:HS dimensioning Total output summer fs.png|900 px|left|thumb|9. <IS_TS id=SumaMocyCWUStacjiWTrybieCWU/>.]]<br clear="all"/>


===The difference between the <IS_TS id=sMocCalkowitaZr/> of the heat source and <IS_TS id=IloscCieplaNiesionaPrzezDzialkeLong/> on the first section from the heat source===





Revision as of 13:56, 15 December 2022

Product InstalSystem 5
Type of article TIP&TRICK
Source for translation 2022-12-14


Problem description

The way in which the heat source is dimensioned depends on the type of designed installation and on the Method of calculating Φ specified in the General data window.

1. Method of calculating Φ selection.


Solution

Heating installations without Flat stations

For dimensioning the heat source the following values should be taken into account:

  • Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard;
    2. Design heat load of building for the installations without Flat stations.

  • The total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified.
    3. Spec. total rooms heat loss ΦH for the installations without Flat stations.

4. Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area for the installations without Flat stations.


Heating installations with Flat stations

For such type of installations there are two variants for the heat source dimensioning in the heating period:

  • If the heat source lacks a buffer tank - heat source dimensioning should adopt the Total output value;
    5. Total output for the installations with Flat stations.

  • If the heat source includes a buffer tank - the indicated Total output value is the peak power that the buffer tank is supposed to deliver to the installation. For dimensioning the heat source the following values should be taken into account:
  • Design heat load of building – in the case when thermal calculations of a building based on Calculations acc. to standard
    6. Design heat load of building for the installations with Flat stations.

  • The total value of: Spec. total rooms heat loss ΦH, Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area - in the case when thermal calculations of a building based on Calculated acc. to coefficient or User specified
    7. Spec. total rooms heat loss ΦH for the installations with Flat stations.

8. Not utilized heat loss of pipe-runs and Losses of radiant systems to outside of source feed area for the installations with Flat stations.


Total output of heat exchangers in flat stations in summer

In summer period, when the flat stations are operating in DHW heating mode, the heating capacity ordered from the heat source can be reduced. The value of Total output of heat exchangers in flat stations in summer can be found in the General results heating.

9. Total output of heat exchangers in flat stations in summer.


The difference between the Total output of the heat source and Heat quantity carried by pipe-run on the first section from the heat source